ALTA Wireless Pressure Meter - 50 PSIG - AA Battery Powered, 900MHZ

MonnitSKU: MNS2-9-W2-PS-050

Price:
$414.05

Description

Monnit wireless pressure meters measure pressure and transmit the pressure measurement to iMonnit. By connecting the Monnit wireless pressure meter to a pressurized gas, liquid or vapor supply line, it can measure the pressure within the line and send data to the iMonnit Online Sensor Monitoring and Notification System. The data is stored in the online system and can be reviewed and exported as a data sheet or graph. User customization allows you to set notifications and alerts from the system so you can know immediately if pressure is above or below an optimal range.

Monnit MNS2-9-W2-PS-050 Features

  • 1,200+ foot range
  • 12+ year battery life
  • 80+ wireless sensors
  • Bank-level AES security
  • Up in 15 easy setup
  • Global ready (900, 920, 868 & 433 MHz)
  • Pressure Transducer Specifications

  • Operating Temperature: 0 to 175°F (-18 to 79°C)
  • Thermal Effect on Reading: ±0.02% FS/°F. (includes zero and span).
  • Media: Gas, Liquid or Vapor
  • Response Time: 50 msec.
  • Stability: 1.0% FS/year (Typ.).
  • Wire Length: 1 Meter shielded cable (between gauge and wireless unit)
  • Accuracy: 0.25% FS; 0.20% RSS; Absolute Ranges: 0.5% FS; 0.35% RSS. (Includes linearity, hysteresis, and repeatability).
  • Maximum Rated Input Voltage: 5.5 V
  • Voltage Range: 0 - 5.2 V
  • Voltage Resolution: ~3 mV
  • Voltage Measurement Accuracy: ± 3% FS
  • Pressure Measurement Accuracy: ± 3% FS
  • User Calibrated Accuracy: +/- 1% FS
  • Process Connection: ¼" NPT-Male Standard
  • Pressure Transducer(s): 50 or 300 PSIG (Others available upon request)
  • Weight: 10.3 oz.
  • Variation Specifications

  • Security: Encrypt-RF® (256-bit key exchange and AES-128 CTR)
  • Max Output Voltage: 5.5 V
  • User Calibrated Pressure Accuracy: ± (0.5% of reading + 0.5% FS)
  • ALTA AA Specifications

  • Battery Type: 2 Replaceable AA 1.5 V Batteries
  • Dimension: 4.375 in x 2.470 in x 1.12 in
  • Supply Voltage: 2.0 - 3.8 V (2 x AA 1.5V Batteries or Optional Power Supply)
  • Battery Life: At 1 hour heartbeat setting, AA batteries will last up to 10 years.**
  • Max Operating Temperature Using AA Alkaline: -18°C to 55°C (0°F to 130°F)
  • Max Operating Temperature Using AA Lithium: -40°C to 60°C (-40°F to 140°F)
  • Optimal Battery Operating Temperature: +10°C to +50°C (+50°F to +122°F)
  • Enclosure Material: ABS
  • ALTA 900 MHz Specifications

  • Operating Frequency: 900 MHz Operating Frequency
  • Certifications: Complies with Part 15 of the FCC Rules. (FCC ID: ZTL-G2SC1)Complies with Industry Canada standards. (IC: 9794A-G2SC1)
  • Device Range: Device Range Up to 1,200 ft. non-line-of-sight, wireless device range*
  • Security: Encrypt-RF® (Diffie-Hellman Key Exchange + AES-128 CBC)